Transformer Turn Ratio Tester

TTR (Transformer Turn Ratio Tester) CHINESE FS3030

FS3030 three-phase transformer turns ratio (TTR) tester. Second-hand unit.

Share This Product :

An FS3030 transformer turns ratio tester for verifying winding ratio, polarity and vector group.

Vector group verification: the part people forget

Turns ratio gets the attention, but a TTR set also confirms phase displacement — the vector group. That matters more than it sounds.

Two transformers operating in parallel must have the same vector group. A Dyn11 and a Dyn1 have a 60° phase difference between their outputs. Paralleling them does not simply share load unevenly — it creates a large circulating current driven by the phase difference, which will damage both transformers, potentially within minutes.

A TTR test catches a mislabelled or incorrectly connected transformer before it is paralleled. A nameplate is not evidence; a measurement is.

Single-phase or three-phase testing

A three-phase set connects once to all three phases and steps through them automatically. On a power transformer with a 33-position tap changer, that is the difference between an afternoon and a full day — and it removes the connection errors that accumulate with repeated re-leading.

Accuracy requirement

Against a 0.5% acceptance limit, an instrument accurate to 0.1% leaves usable margin. One accurate to 0.5% consumes the entire acceptance band in measurement uncertainty.

Condition: second-hand unit. Send the transformer details and required ratings with your enquiry, and IndusGrove will confirm condition and availability.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].