Lightning protection covers two jobs that are frequently confused, specified by different standards, and solved by entirely different equipment. Getting the distinction right is the first step in specifying either.
- A lightning protection system (LPS) intercepts a direct strike and conducts it safely to earth. Air terminals, down conductors, earth electrodes and bonding. Governed by IEC 62305.
- A surge arrester limits overvoltage on an electrical network — from a nearby strike, a switching operation or a fault. It protects equipment insulation, not the building. Governed by IEC 60099-4 for metal-oxide arresters.
A substation with excellent surge arresters and no earthing grid is unprotected. So is a building with a perfect air termination network and no SPDs on the incoming supply.
Lightning protection systems
Air termination and the rolling sphere
The rolling sphere method is the standard design technique: imagine a sphere of defined radius rolled over the structure. Wherever it touches, a strike can land, and those points need protection. The radius depends on the protection level — Level I (20 m) is the most demanding, down to Level IV (60 m).
The protection level is not a preference. It follows from the risk assessment in IEC 62305-2, which weighs strike density, structure size, occupancy and the consequences of failure. A control building housing protection relays and a warehouse holding pallets do not warrant the same level.
Down conductors and separation distance
Down conductors carry the current from the air termination to earth. Two rules dominate:
- Multiple parallel paths reduce the current in each conductor and the resulting voltage rise. Spacing requirements tighten with protection level.
- Separation distance — the minimum gap between the LPS and internal metalwork or cabling. Below it, the lightning current side-flashes across, and it will pick the path through your cable tray. Where the distance cannot be achieved, the metalwork must be bonded instead.
Earthing
The earth termination is where lightning protection succeeds or fails. Design targets are commonly quoted around 10 Ω for an LPS earth, but the figure that matters is the impulse impedance, not the 50 Hz resistance a standard tester measures.
Achieving a low value depends far more on soil resistivity than on the electrode. Rock and dry sand can require deep-driven electrodes, extended horizontal conductors or ground enhancement material where a single rod would be pointless. This is why a soil resistivity survey precedes an earthing design rather than following it.
Exothermic welded joints are specified over mechanical clamps below ground because a bolted connection corrodes, loosens and rises in resistance over years, entirely invisibly.
Surge arresters
Selecting one
Modern arresters are metal-oxide, gapless. Selection turns on four figures:
- Continuous operating voltage (Uc or MCOV) — the voltage the arrester withstands indefinitely. It must exceed the maximum phase-to-earth voltage including any temporary rise, and this is where arresters are most often under-specified.
- Rated voltage (Ur) — the temporary overvoltage capability, typically driven by the earth-fault factor of the system. A solidly earthed network and an isolated-neutral network need very different arresters at the same nominal voltage.
- Nominal discharge current (In) and line discharge class — the energy handling capability
- Protection level (Upl) — the residual voltage at discharge, which must sit adequately below the protected equipment’s insulation withstand with a margin
Polymer or porcelain housing
Polymer (silicone rubber) housings dominate new installations: lighter, resistant to vandalism, and they fail without shattering — a genuine safety advantage in a manned substation. Porcelain retains a following where long-established specifications and proven UV endurance matter.
The mistake that undoes a good arrester
Lead length. The voltage appearing across the protected equipment is the arrester’s residual voltage plus the inductive drop along its connecting leads. At lightning current rise rates, a metre of lead can add several kilovolts.
An arrester with an excellent protection level installed on long, looping leads can deliver worse protection than a modest arrester mounted tight. Keep both the line lead and the earth lead as short and as straight as physically possible.
Surge protective devices (SPDs) for LV systems
On low-voltage installations, IEC 61643 defines three types:
- Type 1 — tested with a 10/350 µs impulse, for the origin of the installation where a direct strike current may be conducted in
- Type 2 — 8/20 µs, for distribution boards
- Type 3 — fine protection close to sensitive equipment, only effective downstream of a Type 2
Types are coordinated, not alternatives. A Type 3 SPD at a workstation with nothing upstream will be destroyed by the first significant surge.
Surge protective devices available on IndusGrove
Zotup (Stezzano, Bergamo, founded 1986) builds surge protection and nothing else, declared to the 2025 editions of IEC 61643-11 and EN IEC 61643-11. Its EPP indicator reports residual performance progressively rather than as a single end-of-life flag, so a device can be replaced while it is still protecting:
- ZotupLimiter L 50/100 — Type 1+2, Iimp 50 kA (10/350 µs), three protection modes
- ZotupLimiter L 13/40 — compact Type 1+2 for sub-distribution, 1 to 4 pole
- IA 25 230 — Type 2 for distribution boards, 25 kA class, 1P to 3+1
- I 100 N-PE spark gap — for TT systems in CT2 insertion mode per HD 60364-534
- ZotupLimiterPV L 13/60 PV — Type 1+2 for photovoltaic DC, 600 V and 1000 V, Y configuration
- ZotupData S-ASI — signalling and data line protection, C1/C2/C3/D1, 6 to 48 V