Lightning protection covers two jobs that are frequently confused, specified by different standards, and solved by entirely different equipment. Getting the distinction right is the first step in specifying either.

A substation with excellent surge arresters and no earthing grid is unprotected. So is a building with a perfect air termination network and no SPDs on the incoming supply.

Lightning protection systems

Air termination and the rolling sphere

The rolling sphere method is the standard design technique: imagine a sphere of defined radius rolled over the structure. Wherever it touches, a strike can land, and those points need protection. The radius depends on the protection level — Level I (20 m) is the most demanding, down to Level IV (60 m).

The protection level is not a preference. It follows from the risk assessment in IEC 62305-2, which weighs strike density, structure size, occupancy and the consequences of failure. A control building housing protection relays and a warehouse holding pallets do not warrant the same level.

Down conductors and separation distance

Down conductors carry the current from the air termination to earth. Two rules dominate:

Earthing

The earth termination is where lightning protection succeeds or fails. Design targets are commonly quoted around 10 Ω for an LPS earth, but the figure that matters is the impulse impedance, not the 50 Hz resistance a standard tester measures.

Achieving a low value depends far more on soil resistivity than on the electrode. Rock and dry sand can require deep-driven electrodes, extended horizontal conductors or ground enhancement material where a single rod would be pointless. This is why a soil resistivity survey precedes an earthing design rather than following it.

Exothermic welded joints are specified over mechanical clamps below ground because a bolted connection corrodes, loosens and rises in resistance over years, entirely invisibly.

Surge arresters

Selecting one

Modern arresters are metal-oxide, gapless. Selection turns on four figures:

Polymer or porcelain housing

Polymer (silicone rubber) housings dominate new installations: lighter, resistant to vandalism, and they fail without shattering — a genuine safety advantage in a manned substation. Porcelain retains a following where long-established specifications and proven UV endurance matter.

The mistake that undoes a good arrester

Lead length. The voltage appearing across the protected equipment is the arrester’s residual voltage plus the inductive drop along its connecting leads. At lightning current rise rates, a metre of lead can add several kilovolts.

An arrester with an excellent protection level installed on long, looping leads can deliver worse protection than a modest arrester mounted tight. Keep both the line lead and the earth lead as short and as straight as physically possible.

Surge protective devices (SPDs) for LV systems

On low-voltage installations, IEC 61643 defines three types:

Types are coordinated, not alternatives. A Type 3 SPD at a workstation with nothing upstream will be destroyed by the first significant surge.

Surge protective devices available on IndusGrove

Zotup (Stezzano, Bergamo, founded 1986) builds surge protection and nothing else, declared to the 2025 editions of IEC 61643-11 and EN IEC 61643-11. Its EPP indicator reports residual performance progressively rather than as a single end-of-life flag, so a device can be replaced while it is still protecting:

Browse and enquire

See current listings under Earthing & Lightning Protection and Surge Arresters.

For a quotation, send the system voltage and earthing arrangement, the equipment being protected, the structure details and any soil resistivity data. For surge arresters, the neutral earthing arrangement matters as much as the nominal voltage.