A Rogowski coil measures alternating current without an iron core. It is an air-cored toroidal winding placed around the conductor; the changing magnetic field induces a voltage proportional to the rate of change of current, and an integrator converts that back into a current signal.
That single design difference — no iron — is the source of every advantage and every limitation the technology has.
What having no iron core changes
It cannot saturate
A conventional current transformer has an iron core that saturates. During a heavy fault, a saturating CT stops reproducing the waveform faithfully at exactly the moment the protection relay most needs an accurate signal — and saturation is a well-known cause of protection maloperation and failure to trip.
A Rogowski coil has nothing to saturate. Its response stays linear from a few amperes to hundreds of kiloamperes, which is why they are increasingly specified for protection applications and for fault studies.
Open circuit is safe
An energised CT with its secondary open develops a lethal voltage across the terminals — the reason CT secondaries must always be shorted before disconnection, and the cause of a great many accidents. A Rogowski coil produces a low-level signal and is inherently safe open-circuited.
It is light, flexible and easy to install
A flexible coil wraps around an existing busbar or cable and clips shut. There is no need to break the conductor, no heavy iron to support, and awkward geometry — multiple parallel cables, rectangular busbars, cramped panels — stops being a problem. On a live board where an outage is not available, this is often the only practical way to measure at all.
The limitation: it cannot measure DC
The output depends on a changing field. A Rogowski coil measures AC only. It also produces a low-level signal requiring an integrator and, usually, a power supply, whereas a CT delivers usable current directly. And its accuracy is more sensitive to positioning than a rigid CT’s.
Positioning is the thing that goes wrong
Two rules decide whether a Rogowski measurement is trustworthy:
- Centre the conductor in the loop. A conductor lying against the coil rather than centred introduces error. Good coils are designed to minimise this, but none eliminates it.
- Close the coil properly and keep the return path correct. A poorly mated closure, or an untidy loop with the cable exiting at an angle, admits error from adjacent conductors.
In a three-phase panel with busbars close together, a badly positioned coil picks up the neighbouring phase and reports a plausible but wrong power factor — a fault that never announces itself, because the numbers look like data.
Types
- Flexible coils — the classic form. Wrap around anything, in a range of loop lengths and cross-section diameters (typically ∅6 mm to ∅14 mm). The larger the cross-section, the higher the output and the better the low-current performance.
- Rigid coils — fixed geometry, better repeatability and accuracy where the conductor position is known and permanent. Suited to switchgear and panel-builder applications.
- Split rigid coils — open and close around an existing conductor while keeping rigid-coil accuracy. The retrofit option where an outage is not available.
- High-voltage resistant coils — additional insulation for placement close to energised conductors
- Welding coils — built for the extreme currents and harsh duty of resistance welding
Where they are used
- Protection relaying — particularly where CT saturation on high fault levels is a design problem
- Power quality analysers and energy loggers — the standard flexible clamp for portable instruments on large or awkward busbars
- Retrofit sub-metering on live distribution boards
- Fault and transient studies, where linear response through the full range matters
- Switchgear and panel building, where rigid coils replace bulky CTs and save space and weight
- Welding and industrial process monitoring
What to specify
- Loop length — must comfortably encircle the conductor or busbar bundle
- Cross-section diameter — drives sensitivity and low-current accuracy
- Current range and accuracy class for the application
- Output — whether the coil is supplied with a matched integrator, and what signal the receiving instrument expects
- Insulation rating and the voltage of the conductor it will sit against
- Bandwidth, where harmonics or transients are being measured
Coil and integrator are a matched pair. Mixing a coil from one maker with an integrator from another gives a reading that is confidently wrong.
Browse and enquire
See current listings under Smart Metering & Grid Intelligence and Energy Meters & Analyzers.
For a quotation, send the conductor size and shape, the maximum current, the accuracy required, the instrument the coil must feed and the system voltage.