A Rogowski coil measures alternating current without an iron core. It is an air-cored toroidal winding placed around the conductor; the changing magnetic field induces a voltage proportional to the rate of change of current, and an integrator converts that back into a current signal.

That single design difference — no iron — is the source of every advantage and every limitation the technology has.

What having no iron core changes

It cannot saturate

A conventional current transformer has an iron core that saturates. During a heavy fault, a saturating CT stops reproducing the waveform faithfully at exactly the moment the protection relay most needs an accurate signal — and saturation is a well-known cause of protection maloperation and failure to trip.

A Rogowski coil has nothing to saturate. Its response stays linear from a few amperes to hundreds of kiloamperes, which is why they are increasingly specified for protection applications and for fault studies.

Open circuit is safe

An energised CT with its secondary open develops a lethal voltage across the terminals — the reason CT secondaries must always be shorted before disconnection, and the cause of a great many accidents. A Rogowski coil produces a low-level signal and is inherently safe open-circuited.

It is light, flexible and easy to install

A flexible coil wraps around an existing busbar or cable and clips shut. There is no need to break the conductor, no heavy iron to support, and awkward geometry — multiple parallel cables, rectangular busbars, cramped panels — stops being a problem. On a live board where an outage is not available, this is often the only practical way to measure at all.

The limitation: it cannot measure DC

The output depends on a changing field. A Rogowski coil measures AC only. It also produces a low-level signal requiring an integrator and, usually, a power supply, whereas a CT delivers usable current directly. And its accuracy is more sensitive to positioning than a rigid CT’s.

Positioning is the thing that goes wrong

Two rules decide whether a Rogowski measurement is trustworthy:

In a three-phase panel with busbars close together, a badly positioned coil picks up the neighbouring phase and reports a plausible but wrong power factor — a fault that never announces itself, because the numbers look like data.

Types

Where they are used

What to specify

Coil and integrator are a matched pair. Mixing a coil from one maker with an integrator from another gives a reading that is confidently wrong.

Browse and enquire

See current listings under Smart Metering & Grid Intelligence and Energy Meters & Analyzers.

For a quotation, send the conductor size and shape, the maximum current, the accuracy required, the instrument the coil must feed and the system voltage.