Contact Resistance

Contact Resistance MicroOhm Meter CA10

CA10 micro-ohm meter for contact and joint resistance measurement. Second-hand unit.

Share This Product :

A CA10 micro-ohm meter for low resistance measurement on contacts, joints and busbar connections.

Why a normal ohmmeter cannot do this

The resistances that matter here are measured in microhms. A healthy circuit breaker contact may sit at 30–50 µΩ; a bolted busbar joint lower still.

An ordinary two-terminal ohmmeter measures the resistance of its own leads and their contact with the surface as well — and those are typically milliohms, hundreds of times larger than the quantity being measured. The reading is dominated by the instrument, not the joint.

The Kelvin four-terminal method

Micro-ohm meters use four terminals: two inject a known current, and two entirely separate leads measure the voltage developed across the joint. Because the voltage-sensing circuit draws essentially no current, the resistance of those leads and their contacts contributes nothing to the measurement.

Placement matters: the voltage probes must sit inside the current probes, otherwise the measurement includes conductor either side of the joint.

Why the test is done at all

Contact resistance rises as contacts erode, oxidise or lose pressure. A joint at four times its healthy resistance dissipates four times the heat at the same current — and a hot joint accelerates its own degradation until it fails, often spectacularly.

Trending the value over time is more informative than any single reading, since the acceptance figure depends on the specific equipment.

Condition: second-hand unit. Send the application and required ratings with your enquiry, and IndusGrove will confirm condition, accessories included and availability.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].