Transformer Bushings

Yash OIP Wall Through Bushing (24 kV – 245 kV)

Wall through OIP bushings from 24 kV to 245 kV, in porcelain or polymer housing to IEC or IEEE. Carries a live conductor through a building wall or barrier in indoor substations, GIS halls and industrial installations.

Share This Product :

Yash OIP Wall Through Bushing (24 kV – 245 kV)

A wall through bushing carries an energised conductor through a wall, roof or earthed barrier while maintaining insulation and a sealed, weatherproof interface. Unlike a transformer bushing it has an air side at both ends, or air on one side and an enclosed room on the other, so both ends need full external insulation and the creepage on each side is specified independently.

Where It Is Used

  • Bringing overhead line or busbar connections into an indoor substation or switch house
  • Feeding through the wall of a GIS hall or transformer bay
  • Industrial plant where the switchgear room is separated from the outdoor yard
  • Test laboratories and workshop high voltage areas
  • Any barrier penetration where a cable termination would be impractical or costly

Typical Specification

  • Voltage class: 24 kV to 245 kV
  • Insulation: oil impregnated paper condenser core
  • Housing: glazed porcelain or polymer, selected independently for each side
  • Standards: IEC 60137:2017 or IEEE C57.19.00/01
  • Mounting: central flange to suit the wall thickness and opening, horizontal or vertical
  • Options: asymmetric creepage where indoor and outdoor pollution levels differ, custom lengths each side, terminal arrangements to suit busbar or line connection

Selection Notes

The two sides of a wall bushing rarely face the same conditions. The outdoor side may sit in coastal salt fog while the indoor side is clean and dry, so specifying a single creepage for both wastes money on one side and risks the other. State the pollution severity, expected temperature and any wash regime for each side separately. Polymer housing on the outdoor side and porcelain indoors is a common and sensible combination.

Ordering Information

Provide rated voltage and current, wall thickness and opening dimensions, orientation, required creepage for each side, terminal arrangement at both ends, and the governing standard. Submit the enquiry through IndusGrove.

Type tested at ILAC accredited laboratories, with more than 140 standardised model type tests available. Supplied against IEC 60137:2017, IEEE C57.19.00/01 and equivalents. Retrofit and interchangeable solutions available for existing bushings of any global make. Contact via IndusGrove with voltage class, current rating, creepage and mounting details.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].