Transformer Bushings

ZDVolt ZDTHPO P&O Thermosiphon High Current Bushing (up to 45,000 A)

Patented Porcelain & Oil (P&O™) thermosiphon bushings for generator step-up transformer terminals, rated to 45,000 A at 1–52 kV under IEC, or 6,000–20,000 A at 15–34.5 kV under ANSI/IEEE C57.19.04. The only field-proven commercially available thermosiphon bushing in the industry.

Share This Product :

ZDVolt ZDTHPO P&O Thermosiphon High Current Bushing (up to 45,000 A)

On a generator step-up transformer the low voltage terminal carries the full machine output at generator voltage — tens of thousands of amperes at modest voltage. The limiting factor is not electrical stress but heat. Resistive loss in the central conductor and eddy heating in the flange and turret must be removed, or the paper insulation and surrounding transformer oil degrade.

What a Thermosiphon Bushing Does Differently

A conventional high current bushing relies on conduction and the surrounding oil to shed heat, which sets a practical ceiling on current rating. The P&O™ (Porcelain & Oil) design uses thermosiphon circulation: oil inside the bushing rises as it warms at the hot conductor, transfers heat at the cooler upper surfaces, and falls back — a passive convective loop with no pump and nothing to fail. Removing heat actively rather than passively is what allows the rating to reach 45,000 A, well beyond conventional designs.

ZDVolt states this is the only field-proven, commercially available thermosiphon bushing solution in the industry, with more than 504,000 installations across the P&O I and P&O II series.

Ratings

  • IEC 60137 and GB/T 4109: 1 kV to 52 kV, 100 A to 45,000 A
  • ANSI/IEEE C57.19.00-2023 and C57.19.04-2018: 15 kV to 34.5 kV, 6,000 A to 20,000 A
  • Housing: porcelain, produced in-house by enhanced cold isostatic pressing
  • Related series: ZDTSEC solid epoxy cast bushings, 1–52 kV at 200–8,000 A IEC, for medium voltage and distribution duty

Field Record

  • P&O II 31,500 A bushing energised in 2016
  • P&O II 24 kV 12,000 A bushings energised on a 765 kV GSU in Ohio, USA, December 2025
  • OIP and P&O II supplied to a 138 kV 204 MVA GSU in Houston, Texas
  • Approximately 500,000 P&O I and 3,000 P&O II units shipped by end of 2025

Applications

  • Generator step-up transformer LV terminals on thermal, hydro, nuclear and combined cycle plant
  • Unit auxiliary and station transformers on large generating units
  • Furnace, rectifier and other high current industrial transformers

Ordering Information

Specify rated continuous current and voltage class, governing standard, busbar or flexible connection interface, oil end length and terminal arrangement, ambient and altitude, and any BCT requirement. On replacements, supply the existing drawing so the turret interface can be reproduced. Submit the enquiry through IndusGrove.

Manufactured at Jurong, Jiangsu, China, with a North American office in Palo Alto, California. Certifications: ISO 9001, ISO 14001, ISO 45001, GOST, UL, and ISO/IEC 17025 accredited laboratories. Average lead time approximately five months. Custom designs and replacement bushings for existing transformers available.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].