Transformer Turn Ratio Tester

CYZB-201A Automatic Transformer Turns Ratio Tester (TTR)

Share This Product :

The Kiyu Power CYZB-201A is a computer-controlled transformer turns ratio tester. Ratio testing is a mandatory item at manufacture, at handover and during maintenance because it is the quickest way to detect turn-to-turn short circuits, open circuits, incorrect connections and tap changer contact faults before the transformer is energised.

The instrument measures ratio, phase displacement and vector group automatically and holds 0.2% accuracy across the 1–1000 range, which is enough resolution to catch a single shorted turn on a distribution winding.

Key specifications

  • Ratio measurement range: 1–10000
  • Accuracy: 0.2% (1–1000), 0.5% (1000–10000)
  • Vector group test range: 1–12
  • Phase test range: 0–360°
  • Power supply: 220 V ±10%, 50/60 Hz
  • Dimensions: 400 × 290 × 170 mm
  • Computer controlled; customisable configurations available

Where it is used

  • Factory routine testing and pre-commissioning
  • Tap changer contact verification across all positions
  • Fault investigation after a protection operation

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.