Neutral Grounding & Earthing Systems

Sieyuan Earthing Transformer for Neutral Grounding

  • Zig-zag and wye-delta earthing transformers that create an artificial neutral on delta-fed networks.
  • High impedance to positive sequence, low impedance to zero sequence — invisible in service, a defined path on fault.
  • Oil-immersed for outdoor substations or dry type for indoor switchrooms.
  • Neutral taken to a grounding resistor, arc suppression coil or current limiting reactor.
  • Auxiliary supply capability available on wye-delta units.
  • Supplied as a coordinated package with neutral CT and earth fault protection.

Share This Product :

Sieyuan Earthing Transformer (Grounding Transformer)

Most medium voltage networks are fed from a delta winding and therefore have no neutral point to earth. An earthing transformer creates one. It is the enabling component for every form of impedance earthing — resistance, resonance or reactance — on a network that does not have a neutral of its own.

How It Works

The standard construction is a zig-zag (interconnected star) winding. Under balanced conditions the zig-zag presents a very high impedance to positive and negative sequence current, so it draws almost nothing and behaves as if it were not there. To zero sequence current it presents a low impedance, giving earth fault current a defined path back to the artificial neutral. That asymmetry is the whole design: invisible in normal service, a solid return path the instant a phase touches earth.

A wye-delta construction achieves the same result with a closed delta tertiary and is often preferred where an auxiliary supply is also wanted, since the same unit can feed station auxiliaries while no earth fault is present.

Where the Neutral Goes

The artificial neutral is rarely earthed solidly. It is taken to one of three devices depending on the earthing philosophy:

  • Neutral grounding resistor — fixes the earth fault current at a chosen value, damps arcing overvoltages, and gives protection a current it can grade on. The dominant choice for industrial and renewable collector networks.
  • Arc suppression coil (Petersen coil) — tunes against the network capacitance so transient earth faults self-extinguish and the network keeps running. Common on overhead distribution with high fault rates.
  • Current limiting reactor — used where the earth fault current must be reduced but a resistor’s losses are unacceptable.

Construction

  • Zig-zag or wye-delta winding configuration to suit the earthing study
  • Oil-immersed construction for outdoor substation installation, or dry type for indoor and enclosed switchrooms
  • Short time zero sequence current rating matched to the protection clearing time, typically 10 seconds
  • Neutral bushing sized and insulated for the neutral device that follows it
  • Auxiliary loading capability available on wye-delta units
  • Supplied with neutral current transformer and earth fault protection relay when ordered as a package

Applications

  • Delta-fed 6.6 kV, 11 kV and 33 kV industrial distribution boards
  • Wind and solar plant collector networks, where the MV collector system has no natural neutral
  • Battery energy storage and inverter-fed plant requiring a defined earth reference
  • Generator step-up arrangements and power plant auxiliary systems
  • Retrofitting an earthing philosophy onto an existing unearthed network

Reference

33 kV earthing transformer with neutral grounding resistor supplied for Saudi PIF renewable energy projects, installed and commissioned on site.

Ordering Information

Supply the earthing study if one exists. Otherwise state the system nominal voltage, the network zero sequence capacitance or total cable length, the earth fault current and time rating required, whether the neutral device is a resistor, arc suppression coil or reactor, indoor or outdoor installation, any auxiliary load to be supplied, and the governing standard. Submit the enquiry through IndusGrove.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].