High Voltage / Indoor

Zhengchao KYN27-12 Metal-Clad Withdrawable Switchgear 12 kV

12 kV air-insulated metal-clad withdrawable switchgear, 630 to 4000 A, up to 40 kA, IAC AFLR with LSC2B and PM partition class.

Share This Product :

The Zhengchao KYN27-12 is an indoor metal-clad withdrawable switchgear panel for three-phase AC systems at 12 kV and 50/60 Hz, used to receive and distribute electrical energy and to control, protect and monitor circuits. The panel is fitted with the VS1 vacuum circuit breaker that Zhengchao develops and builds in-house.

Five electrical interlocks are provided: they prevent the breaker truck being racked in or out on load, prevent false opening and closing of the circuit breaker, prevent energising or de-energising the breaker while the earthing switch is closed, and prevent access to a live compartment. The design carries internal arc classification IAC AFLR, loss of service continuity category LSC2B and partition class PM, which together describe how the panel behaves in an internal arc fault, how much of the board stays in service during maintenance, and whether the partitions between compartments are metallic.

Main technical parameters published by the manufacturer: rated voltage 12 kV; rated frequency 50/60 Hz; main busbar and branch busbar rated current 630, 1250, 1600, 2000, 2500, 3150 or 4000 A; rated power-frequency withstand 42 kV phase-to-phase and to earth, 48 kV across the isolating distance; rated lightning impulse withstand 75 kV phase-to-phase and to earth, 85 kV across the isolating distance, extendable to 95 and 110 kV on request; rated short-time withstand current 25, 31.5 or 40 kA for 4 s; rated peak withstand current 63, 80 or 100 kA; rated short-circuit breaking current 25, 31.5 or 40 kA; rated short-circuit making current 63, 80 or 100 kA peak; internal arc 25 kA for 1 s, 31.5 kA for 1 s or 40 kA for 1 s; degree of protection IP2X between compartments and IP4X for the enclosure.

Panel height is 2250 mm across the 630 to 4000 A range. Width is 650 mm for branch busbar currents up to 1250 A, 800 mm from 1250 to 2000 A and 1000 mm at 2000 A and above. Depth is 1400 mm below 4000 A, 1600 mm at 4000 A and above, and 1700 mm for overhead-line panels at 4000 A and above. Weight is 800 kg at 1250 A and 1000 to 1100 kg at 3150 A and above.

Applications include power plants, substations, industrial and mining enterprises and high-rise buildings.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].