| Feature | Specification |
| Models | APM800, APM801, APM810, APM830 |
| Accuracy Class | APM800/APM810: Class 0.5s, APM801/APM830: Class 0.2s |
| Voltage Input | 3P3W / 3P4W (Rated 100V, 110V, 400V, 690V) |
| Current Input | 1A / 5A AC via CT, 1.2× continuous, 10× for 1s |
| Frequency | 45–65Hz |
| Harmonic Analysis | 2nd to 63rd (accuracy: 1% up to 42nd, 2% from 43rd) |
| Power Quality | Unbalance, crest factor, waveform distortion, K-factor, sequence components |
| Energy Measurement | Active/reactive, four-quadrant metering |
| Data Logging | TF card support (up to 32GB), 128 events & 16 alarms stored |
| I/O Options | Standard: 2DI + 2DO; Optional: 8DI + 2DO, 8AI + 4AO |
| Analog Input/Output | 0–5V, 0–20mA, 4–20mA, 1–5V, Class 0.5%, ≤500Ω load |
| Communication Interfaces | RS485 (Modbus-RTU), Profibus-DP, Ethernet (Modbus-TCP, HTTP, DHCP) |
| Pulse Output | 4000 imp/kWh (5A), 8000 imp/kWh (1A), opto-isolated |
| Auxiliary Power Supply | AC/DC 85–265V or AC/DC 115–415V (P2 models) |
| Power Consumption | ≤15VA |
| Operating Temperature | -20°C to +65°C |
| Storage Temperature | -20°C to +70°C |
| Humidity | ≤95% RH (non-condensing) |
| Protection Level | IP54 (front), EMC Level 4 |
| Installation | Panel mount, 96×96mm front panel |
No additional information.