Cable Test Set

BAUR frida TD Portable VLF Tester and Diagnostics Device

22 kg portable VLF truesinus tester, 1–26 kVrms / 36 kVpeak, with tan delta and partial discharge measurement for cables up to 15 kV at 3 x U0.

Share This Product :

frida TD is the portable member of BAUR’s VLF family — the unit a two-person crew carries down a manhole. At roughly 22 kg including the HV connection cable, it delivers laboratory-grade diagnostics from a case a technician can lift alone.

Specification

  • VLF truesinus® 1 – 26 kV rms (36 kV peak)
  • VLF cable testing at 3 × U0 for cables up to 15 kV
  • tan δ measurement range 1×10-4 to 21,000×10-3 at 0.1 Hz; accuracy 1×10-4, resolution 1×10-6
  • Load range 10 nF – 8 µF
  • Monitored Withstand Test with dissipation factor and partial discharge measurement
  • Automatic detection and compensation of leakage currents
  • IP54 when closed; 438 × 456 × 220 mm; max. 300 VA from 100 – 260 V, 50/60 Hz; USB 2.0

Where it fits

Commissioning tests on newly laid MV cable and joints, acceptance testing after a repair, and routine condition assessment on 11 kV and 15 kV distribution feeders. Automatic leakage-current compensation matters in the field: on a wet or contaminated termination, an uncompensated instrument reports a fault that is not in the cable.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].