Cable Fault Locator

BAUR shirla Cable Sheath Testing and Fault Location System

Sheath test and fault location device generating pulsed voltages to 10 kV, with Murray and Glaser bridge pre-location and step-voltage pin-pointing.

Share This Product :

shirla is BAUR’s dedicated cable sheath testing and fault location device. A damaged outer sheath is not an outage on the day it happens — it is a slow ingress of moisture that becomes an outage a year later, which is exactly why sheath testing is written into most utilities’ commissioning and periodic-inspection regimes.

Capability

  • Generates pulsed voltages up to 10 kV, with four selectable pulse patterns plus adjustable switch-on delay and operating time
  • Fault pre-location by the bridge principle after Murray and Glaser, optimised for power cables but usable on control and lightning-protection cable
  • Fault distance displayed directly in metres; cable sections can be entered by length, conductor cross-section and material to sharpen the result
  • Zero balance and evaluation run automatically — no manual bridge nulling
  • Pulsed output drives the step-voltage method for pin-pointing earth-contact faults, working directly with the BAUR protrac pin-pointing system

Practical note

Sheath faults are pre-located electrically and then pin-pointed on the surface. shirla covers both halves of that job, which is why it is normally specified alongside protrac rather than on its own.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.