Multi-Circuit & Branch Circuit Meters

MCM283R 8-Circuit Commercial Building Energy Monitor

Share This Product :

The Blue Jay MCM283R is built around 8 main circuits and measures up to 8 three-phase or 24 single-phase circuits in real time. Phases can be related to each other across channels, so a commercial complex billing tenants on individual phases can be metered without one meter per phase.

RS485 and RJ12 interfaces are built in, with Wi-Fi, Ethernet, Zigbee and 4G available as alternatives. The 7.62 mm voltage and current power terminals keep installation straightforward in a crowded distribution board.

Where it is used

  • Commercial complex and mall tenant billing
  • Per-phase allocation in mixed-tenancy buildings
  • Building energy management system data collection

Key specifications

  • Auxiliary supply: 85–265 V AC/DC, 45–65 Hz, burden < 6 VA
  • Current input: 100 mA / 333 mV CT (5 A CT option on selected models), burden < 0.1 W
  • Voltage input: direct 30–450 V AC line-to-line
  • Frequency: 45–65 Hz
  • Accuracy: U / I / P / Q 0.5% (0.2% optional); frequency 0.1%
  • Energy accuracy: active Class 1.0, reactive Class 2.0
  • Safety: CAT III 300 V, 4 kV withstand
  • Communication: RS485 Modbus RTU; Ethernet, Wi-Fi, 4G or Zigbee optional

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at [email protected].