Share This Product :
| Feature | Specification |
| Model | DTSD1352-xSyD |
| Voltage Rating | AC 3×220/380V |
| Current Input | AC 250A, 100A (via external CTs) |
| Input Overload Capacity | 1.2× continuous; 10× for 1s |
| Power Consumption | ≤0.5VA per channel |
| Frequency Range | 45–65Hz; accuracy: 0.05Hz |
| Measurement Accuracy | Voltage & Current: Class 0.5 |
| Harmonic Measurement | 2nd–31st order, accuracy ±1% |
| Alarm Functions | Overvoltage, overcurrent, phase loss, DI linkage |
| Digital Inputs (DI) | 4-channel passive dry contact input |
| Digital Outputs (DO) | 2-channel relay output (AC 250V/3A or DC 30V/3A) |
| Pulse Output | Optocoupler with open collector |
| Communication Interface | RS485, Modbus-RTU |
| Baud Rate | 1200–38400 bps |
| Auxiliary Power Supply | AC/DC 85–265V |
| Operating Temperature | -20°C to +60°C |
| Storage Temperature | -40°C to +70°C |
| Relative Humidity | ≤95%, no condensation |
| Altitude | ≤2500 meters |
| Installation | DIN-rail (35mm) |
| Dimensions (mm) | 87.8 (L) × 72 (W) × 71.5 (H) |
No additional information.