An earth leakage relay with a separate core balance current transformer, giving adjustable leakage current and time settings rather than the fixed characteristic of a moulded RCD.

Adjustability is the point. A fixed 30 mA RCD is correct for personnel protection on a socket circuit and useless on a motor feeder, where normal capacitive leakage will trip it constantly. An adjustable earth leakage relay lets the setting be chosen against the actual standing leakage of the installation, which is what makes earth fault protection workable on plant with long cable runs, variable speed drives or extensive screened cabling.

What to specify

  • Leakage current setting range required
  • Time delay range
  • Core balance CT window size for the cable or busbar
  • Auxiliary supply voltage
  • Output contact configuration and whether trip or alarm only

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at info@indusgrove.com.