Overhead Conductor

SeaTrust Bare Overhead Conductor (ACSR, AAC, AAAC)

Bare overhead conductor in ACSR, AAC, AAAC and ACAR constructions for transmission and distribution lines, supplied on drums with test certificates to IEC and ASTM standards.

Share This Product :

SeaTrust Bare Overhead Conductor (ACSR, AAC, AAAC)

The conductor is the largest single material item on any overhead line by weight and usually by value. Choosing between the standard constructions is a trade-off between current carrying capacity, mechanical strength, corrosion behaviour and cost.

Choosing the Construction

  • ACSR — aluminium conductor, steel reinforced. Aluminium strands around a galvanised steel core. High strength for the weight, so it spans further and needs fewer structures. The standard choice for transmission and long distribution spans. The steel core is a corrosion liability in coastal and industrial air unless greased or specified with heavier galvanising.
  • AAC — all aluminium conductor. Best conductivity per unit weight and excellent corrosion resistance, but low strength, so it suits short spans and urban distribution where structures are close together.
  • AAAC — all aluminium alloy conductor. A middle path: better strength than AAC, better corrosion resistance than ACSR because there is no steel. Widely specified for coastal networks and increasingly preferred where lifetime maintenance is being costed properly.
  • ACAR — aluminium conductor, alloy reinforced. Alloy strands replace the steel core.

Specification

  • Constructions: ACSR, AAC, AAAC, ACAR
  • Sizes: distribution through transmission cross sections; state the code name or the size required
  • Standards: IEC 61089, ASTM B231/B232/B399, BS 215 and equivalents
  • Packing: wooden or steel drums, lengths to suit stringing sections
  • Documentation: works test certificates including resistance, tensile and dimensional results

A Note on Conductor Selection

Conductor choice is usually made on first cost, and that is often the wrong basis. Line losses are paid for every hour of the asset’s life, and a larger or lower-resistance conductor that costs more at purchase frequently pays back many times over in reduced I²R losses. On lines being uprated or reconductored, run the thermal and sag check against the existing structures before defaulting to like-for-like replacement — a larger conventional size will often carry the required current within the original tower loading, and that comparison is cheaper to make on paper than to discover on site.

Ordering Information

State the construction and size or code name, the governing standard, drum lengths required, greasing specification for ACSR, and the destination port. Where the conductor is for a specific line, supplying the line design allows the ampacity and sag-tension assumptions to be checked. Submit the enquiry through IndusGrove.

Two production bases at Yueqing and Lishui, Zhejiang, with more than 1,500 staff including 370 engineers. Project experience across Kenya, Uganda, Rwanda, Burundi, Congo DRC, South Africa, Angola, Sierra Leone, Mauritania, South Sudan, Bangladesh, Myanmar, Thailand and Albania. Design and project support team available. Contact via IndusGrove with the line design, bill of quantities and destination.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at info@indusgrove.com.