Oil-Immersed Transformers

Trafo Elettro Oil Immersed Transformers with Conservator

Share This Product :

Trafo Elettro also build oil-immersed transformers in the classic conservator configuration, where an expansion tank above the main tank absorbs the volume change of the oil as it heats and cools.

Conservator designs remain the correct choice above the distribution ratings and wherever the specification calls for Buchholz protection, oil sampling in service, or on-load tap changing — none of which a sealed tank accommodates. The trade is maintenance: the breather needs attention, and the oil is exposed to atmosphere through it.

Technical data

ConstructionMain tank with conservator (expansion) tank
FittingsHV and LV bushings, off-load tap changer, earthing terminal, breather
ProtectionAccepts Buchholz relay in the conservator pipe
ServicePermits in-service oil sampling and treatment
InstallationIndoor or outdoor
Design intentAccessories pre-wired and positioned to reduce installation cost

Specify with your enquiry

  • Rated power, voltage ratio, vector group, frequency and impedance
  • Whether Buchholz, winding temperature indicator and pressure relief are required
  • On-load or off-circuit tap changing, and the tapping range
  • Cooling class: ONAN, ONAF or ONAN/ONAF dual rating
  • Insulating fluid and whether a dehydrating breather or a sealed conservator bag is specified

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.