Converter Transformers

Wujiang HVDC Converter Transformer (±500 kV / ±800 kV)

Converter transformers for HVDC transmission schemes, in service at ±500 kV (283.7 MVA) and ±800 kV (415 MVA). Valve-side windings designed for the combined AC and DC field stress and harmonic loading of a converter station.

Share This Product :

Wujiang HVDC Converter Transformer (±500 kV / ±800 kV)

The converter transformer is the interface between the AC network and the valve hall of an HVDC scheme. It is the most demanding transformer in the power system: the valve-side winding carries a superimposed DC voltage on top of the AC stress, sees heavy harmonic current from the converter bridges, and must tolerate polarity reversal in line-commutated designs. Wujiang Transformer manufactures converter transformers at UHVDC voltage levels, with units in service at ±500 kV / 283.7 MVA and ±800 kV / 415 MVA.

What Makes a Converter Transformer Different

  • Combined AC and DC insulation design. Valve-side insulation must withstand DC and polarity reversal stress as well as AC, which changes the entire oil and pressboard barrier arrangement compared with a conventional power transformer.
  • Harmonic loading. Converter operation injects characteristic harmonics that raise eddy and stray losses. Winding transposition, magnetic shunts and tank shielding are designed for the resulting additional heating.
  • High short-circuit duty. Converter transformers see repeated through-faults from valve-side events, so mechanical strength governs the design.
  • Wide-range on-load tap changer. HVDC control requires a large tapping range with high step count under continuous duty.
  • Valve-side bushings. DC bushings entering the valve hall carry particular design and interface requirements.

Typical Specification

  • DC voltage class: ±500 kV and ±800 kV; other classes to project specification
  • Rating: units supplied at 283.7 MVA and 415 MVA
  • Configuration: single-phase two-winding and three-winding, Y-Y and Y-D valve windings
  • Cooling: ODAF typical for converter duty
  • Tap changer: wide-range on-load, high step count
  • Standards: IEC 61378-2 for converter transformers, plus project specification

Related UHV Capability

The same works produces 1000 kV / 1,000,000 kVA AC transformers and 1100 kV shunt reactors, and has built a 2000 kV 800 MVA single-phase testing transformer. That UHV manufacturing and testing base is what makes converter transformer production at ±800 kV feasible in the first place — few plants worldwide are equipped for it.

Applications

  • LCC HVDC transmission terminals and back-to-back converter stations
  • Long distance bulk power corridors and cross-border interconnectors
  • Offshore wind HVDC export schemes
  • Asynchronous grid interconnection

Requesting a Quotation

HVDC converter transformers are engineered to the scheme, not selected from a catalogue. Provide the DC voltage and power rating, converter configuration, valve-side winding arrangement, tapping range, harmonic spectrum, transport limits and the governing standard. Submit your specification through IndusGrove.

Designed and tested to IEC, ANSI/IEEE, GB and BS standards, or to the customer technical specification. Full type, routine and special testing available in-house, including sudden short-circuit testing. Contact via IndusGrove for capacity, voltage ratio, vector group and delivery.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at info@indusgrove.com.