Ring Main Units (RMU)

Zhengchao ZCKQG-12 Dry-Air Insulated Ring Main Unit 12 kV

SF6-free 12 kV ring main unit insulated with dry air at 0.02 MPa. 630 A, 20/25 kA, IP67 sealed tank, LSC2.

Share This Product :

The Zhengchao ZCKQG-12 is a 12 kV ring main unit that replaces SF6 with dry air as the insulating medium. Because dry air has a much lower dielectric strength than SF6, an SF6-free design of the same rating either grows in size or works harder on field grading; the ZCKQG-12 operates at a rated inflation pressure of 0.02 MPa against 0.035 MPa for the equivalent SF6 unit, and keeps the same 420 mm cabinet width as the 24 kV SF6 model at 630 A.

The value of the design is regulatory rather than electrical. SF6 has a global warming potential in the tens of thousands and is being restricted in an increasing number of markets, so utilities specifying new medium-voltage switchgear are steadily moving toward alternative gases and vacuum. A dry-air unit carries no F-gas handling, leak-reporting or end-of-life recovery obligation.

Main technical parameters published by the manufacturer: rated voltage 12 kV; rated frequency 50/60 Hz; rated current 630 A; rated power-frequency withstand 42 kV phase-to-phase and to earth, 48 kV across the isolating distance; rated lightning impulse withstand 75 kV phase-to-phase and to earth, 85 kV across the isolating distance; rated short-circuit breaking current 20 and 25 kA with 30 breaking operations; rated short-circuit making current 50 and 63 kA; single capacitor bank breaking 630 A, back-to-back 400 A; cable charging breaking current 50 A; rated operating sequence O-0.3s-CO-3min-CO; rated gas pressure 0.02 MPa at 20 °C with a minimum functional level of 0.01 MPa; sealed box IP67, enclosure IP4X; annual leakage rate no more than 0.1%; auxiliary supply AC 380 V or AC 220 V; control supply DC 110 V, DC 220 V or AC 220 V; loss of service continuity category LSC2.

Cabinet dimensions at 630 A and below are 420 mm wide by 2000 mm high by 850 mm deep, weight 300 kg.

Applications include utility secondary distribution where SF6-free equipment is specified, commercial and public buildings, and networks in jurisdictions restricting fluorinated greenhouse gases.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.

Manufacturers may request an amendment or the removal of any listing at info@indusgrove.com.