Ring Main Units (RMU)

Zhengchao ZCSF-12 SF6 Gas-Insulated Ring Main Unit 12 kV

12 kV, 630 A SF6 gas-insulated ring main unit with IP67 sealed tank, 20/25 kA breaking capacity and LSC2 service continuity.

Share This Product :

The Zhengchao ZCSF-12 is a metal-enclosed, gas-sealed ring main unit using low-pressure SF6 as the insulating medium. High-voltage components are enclosed in a welded tank sealed to IP67, so the live parts are protected from moisture and dust and the unit is designed to run maintenance-free across a wide range of ambient conditions and altitudes. The switchgear enclosure itself is rated IP4X and the annual gas leakage rate is quoted at no more than 0.01%.

The circuit-breaker function uses a solid-sealed pole with an embedded vacuum interrupter, which keeps the structure compact and removes the interrupter from the gas volume. An intelligent control and protection unit can be fitted to combine control, protection, measurement and communication in the cubicle, which is what allows the unit to be used as a distribution-automation node rather than a passive switch.

Main technical parameters published by the manufacturer: rated voltage 12 kV; rated frequency 50/60 Hz; rated current 630 A; rated power-frequency withstand 42 kV phase-to-phase and to earth, 48 kV across the isolating distance; rated lightning impulse withstand 75 kV phase-to-phase and to earth, 85 kV across the isolating distance; control and auxiliary circuit withstand 2 kV; rated short-circuit breaking current 20 and 25 kA with 30 breaking operations; rated short-circuit making current 50 and 63 kA; single capacitor bank breaking 630 A and back-to-back 400 A; cable charging breaking current 50 A; rated operating sequence O-0.3s-CO-3min-CO; rated gas inflation pressure 0.035 MPa at 20 °C with a minimum functional level of 0.01 MPa; auxiliary supply AC 380 V or AC 220 V; control supply DC 110 V, DC 220 V or AC 220 V; loss of service continuity category LSC2.

Cabinet dimensions at 630 A and below are 450 mm wide by 2200 mm high by 750 mm deep, with a weight of 300 kg. The manufacturer notes that cabinet dimensions may be adjusted for the installation location and component configuration, and that specific lightning impulse withstand requirements should be confirmed before ordering.

Typical applications are urban and industrial secondary distribution, power plants, substations, commercial buildings and industrial facilities where a compact, sealed 12 kV switching node is required.

No additional information.

Need a quotation for this product?

Send us your specification and we route the enquiry straight to the manufacturer’s export team. Requesting a quotation through IndusGrove is free.

Independent listing. IndusGrove is an independent B2B directory for the power, electrical and renewable energy industry. We are not a distributor, agent or authorised reseller for the manufacturers listed here, and we do not hold stock. Manufacturer names, brand names, model numbers and trademarks are the property of their respective owners and appear here for identification and reference only.

Product information is compiled from publicly available manufacturer sources and may change without notice. Verify all specifications, ratings and compliance data with the manufacturer before purchase. Enquiries submitted through this page are referred to the manufacturer or its authorised channel.